First Notice | 9/23/2016 | 9/23/2016 | 10/5/2016 | | DONE |
Tom Saunders
|
|
|
This permit finaled on the web by Todd Sellman
|
Final | 9/22/2016 | 9/23/2016 | 9/23/2016 | A | PASS |
Tom Saunders
|
|
|
Tomplease call 30 minutes prior for access Phone #: ###-####
ok to final
|
Override - Parcel Holds | 9/22/2016 | 1/1/1900 | 9/22/2016 | | |
|
|
|
as per Daryl DeGrange ok to schedule inspection
|
Conference | 9/21/2016 | 9/21/2016 | 9/21/2016 | P | DONE |
Daryl DeGrange
|
|
|
Todd-conference only Phone #: ###-#### Discussed NEC 210.52 Baseboard heaters stall not be located below receptacles. BCC 4-05-32 Code violation not to be retained
|
Final | 9/19/2016 | 9/19/2016 | 9/19/2016 | P | FAIL |
Eric Story
|
|
|
would like call ahead; Todd Phone #: ###-#### 210.52 No receptacle shall be above a baseboard heater 4-05-32 No violation shall be retained, receptalces shal be blank off
|
Override - Parcel Holds | 9/19/2016 | 1/1/1900 | 9/19/2016 | | |
|
|
|
electrical fees paid
|
Issue PAID IN FULL permit | | | 7/25/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 7/25/2016 | | |
|
|
|
|