Temporary Service | 7/26/2016 | 7/27/2016 | 7/27/2016 | A | PASS |
James Ady
|
|
|
Corrections made Phone #: ###-#### Inspection requested via web by Darren Larsen t/s u/g n ok
|
Temporary Service | 7/25/2016 | 7/26/2016 | 7/26/2016 | A | FAIL |
Eric Story
|
|
|
Darren Phone #: ###-#### 110.12(a) all unused openings shall be closed 250.53(g) all 8' of ground rod shall be in contact with the earth
|
Application received | | | 7/25/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 7/25/2016 | | DONE |
|
|
|
|
First Notice | 7/27/2016 | 7/27/2016 | | | |
James Ady
|
|
|
|