Final | 2/28/2017 | 2/28/2017 | 2/28/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by PAUL PINNEY....
ok to final
|
Electrical Rough-In | 1/27/2017 | 1/27/2017 | 1/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
I need a grid ceiling inspection. Phone #: ###-#### Inspection requested via web by PAUL PINNEY Grid rough in ok cover
|
Permanent Service | 11/29/2016 | 11/30/2016 | 11/30/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by PAUL PINNEY Main breaker AIC rated 25K with 27K line to ground, 25K Line to Line listed on print. Asked contractor to call Idaho Power for actual rating. Will approve for heat so water lines don't freeze. Must verfy and post for final. p/s u/g n ok
|
Electrical Rough-In | 10/3/2016 | 10/4/2016 | 10/4/2016 | A | PASS |
Rock A. Hudson
|
|
|
Please call before you arrive so I can be there for access. Phone #: ###-#### Inspection requested via web by PAUL PINNEY Contractor to call in upstairs break room ceiling when boxes are installed for non IC rated cans. All walls and hard lids except upstairs ceiling rough in ok cover
|
Issue PAID IN FULL permit | | | 8/9/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/9/2016 | | DONE |
|
|
|
This permit was created on the web by PAUL PINNEY
|
First Notice | 2/28/2017 | 2/28/2017 | | | |
Tom Saunders
|
|
|
|