Final | 1/26/2017 | 1/27/2017 | 1/27/2017 | A | PASS |
Eric Story
|
|
|
Access is 2173 at Lockbox at the front entry. Phone #: ###-#### Inspection requested via web by Paula Gratiot Correctgions fixed final ok
|
Final | 1/3/2017 | 1/4/2017 | 1/4/2017 | A | FAIL |
Eric Story
|
|
|
Lock box is beside front steps and hose spigot. Key code is 2173. Phone #: ###-#### Inspection requested via web by Paula Gratiot 314.20 Box extenders required for kitchen 210.8 All 120v receptacles in kitchen shall have GFCI protection 406.4 tamper proof recpetacles required when changed out
|
Electrical Rough-In | 8/22/2016 | 8/23/2016 | 8/23/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Paula Gratiot Rough in ok cover
|
Electrical Rough-In | 8/16/2016 | 8/17/2016 | 8/17/2016 | A | FAIL |
Rock A. Hudson
|
|
|
key in lock box by front entrance. code is 2173 Phone #: ###-#### Inspection requested via web by Paula Gratiot Failed for the following- 210.52 dining outlet needs added in open wall. 314.23(B)(1) replace boxes in multiple locations that have screws driven through the box for support. 210.11(C)(3) Walls are open in up bath, need to update 20a GFI circuit supplying vanity. 4. 210.52 outlet needs added to left of sliding door upstairs, over 6'.
|
Issue PAID IN FULL permit | | | 8/11/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/11/2016 | | DONE |
|
|
|
This permit was created on the web by Paula Gratiot
|