Final | 8/25/2016 | 8/26/2016 | 8/26/2016 | P | PASS |
Mark Moncarr
|
|
|
Mike is the contact his cell no. is ###-#### Phone #: ###-#### Inspection requested via web by Shawna Gates panel re-located as per Eric, has proper labeling. final ok
|
Final | 8/22/2016 | 8/23/2016 | 8/23/2016 | A | FAIL |
Mark Moncarr
|
|
|
Please call Mike 1/2 hour before inspection at ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates 110.26 work space, heat ducting directly above panel
|
Issue PAID IN FULL permit | | | 8/22/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/22/2016 | | DONE |
|
|
|
This permit was created on the web by Shawna Gates
|
First Notice | 8/26/2016 | 8/26/2016 | | | |
Mark Moncarr
|
|
|
|