Final | 12/21/2016 | 12/22/2016 | 12/22/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Corrections made final ok
|
Final | 12/16/2016 | 12/21/2016 | 12/21/2016 | A | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot...
1) lock outs need applied to overcurrent protection of hard wired appliances 2) disposal oulet must be readily accessible 3) panel shall be labelled clear and legible to specify specific circuit 4) A/C disconnects and over current device shall be labelled for each seperate A/C 5) overcurrent device for A/C is to large 6) outlets serving master bath sinks cannot be enclosed in cabinets...210.52(D) 7) future 50A circuit shall have GFI protection either in panel or at disconnect
|
Rough-In Permanent Service | 9/16/2016 | 9/19/2016 | 9/19/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot Correctiions made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 9/16/2016 | 9/16/2016 | 9/16/2016 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Barbara Szurgot 314.16 Box fill. 3 single gang Kitchen, cook top and family rm. 320.23 A Cable ran in accessable attic with in 6ft of scuttle hole shall be protected by gaurd strips
|
Issue PAID IN FULL permit | | | 8/31/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 8/31/2016 | | DONE |
|
|
|
This permit was created on the web by Barbara Szurgot
|