Final | 1/4/2017 | 1/4/2017 | 1/4/2017 | P | PASS |
Tom Saunders
|
|
|
Tyler Phone #: ###-####...
all corrections made...ok to final
|
Electrical Rough-In | 1/3/2017 | 1/4/2017 | 1/4/2017 | A | PASS |
Tom Saunders
|
|
|
Tyler Phone #: ###-####...
ok to cover open sheetrock areas and replace outlets that were removed to verify right wire...oultet rewired to correct wire
|
Conference | 1/3/2017 | 1/3/2017 | 1/3/2017 | A | DONE |
Daryl DeGrange
|
|
|
Homeowner removed a portion of sheetrock for concealed electrical wiring inspection. Discovered installed dinning room receptacle is on with bedroom 15 ampere branch circuit, Homeowner agreed to refeed from existing 20 ampere small applances circuit. Call in for rough-in inspection when completed.
|
Final | 12/15/2016 | 12/15/2016 | 12/15/2016 | P | FAIL |
Tom Saunders
|
|
|
Tyler Phone #: ###-####...
Both dishwasher circuits or circuit need breaker lockouts installed
oven circuit needs breaker lockout installed
panel for addition needs labelling
all new outlets installed shall be of tamper resistant type
future 30a 240v circuit needs to be put on a 2-pole breaker to turn off both circuits simultaneously
A final inspection can not be done until building permit hold is satisfied with city of boise
|
Conference | 9/6/2016 | 9/7/2016 | 9/7/2016 | P | DONE |
Eric Story
|
|
|
Tyler Phone #: ###-#### Discussed code layout on kitchen countertop. Also informed owner that he will be required to obtain plumbing and hvac permits for work that will be done. Also informed him about the state statue on him having to live in residence for minimun of two years.
|
Application received | | | 9/2/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 9/2/2016 | | DONE |
|
|
|
|