Final | 11/9/2016 | 11/10/2016 | 11/10/2016 | A | PASS |
Rock A. Hudson
|
|
|
1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Duplicate request Final ok
|
Final | 11/9/2016 | 11/10/2016 | 11/10/2016 | A | PASS |
Rock A. Hudson
|
|
|
1001E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
Final | 11/8/2016 | 11/9/2016 | 11/9/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk 210.8- All receptacle outlets located in kitchen area that serve counter top areas shall have GFCI protection. Front outdoor receptacle as well. 314.21- Drywall shall be repaired where open around boxes more than 1/8". Dryer, 2 up bed, 1 low in kitchen area. 406.6- Washer receptacle missing cover plate. 408.4 Circuit directory shall be complete. Trim back soffit receptacle.
|
Rough-In Permanent Service | 9/12/2016 | 9/13/2016 | 9/13/2016 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 9/12/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/12/2016 | | DONE |
|
|
|
This permit was created on the web by Alan Lusk
|