Information based on query as of Tuesday, July 16, 2024.
Permit Information
Permit NumberELE16-02971
StatusFinaled
Name B & B ELECTRIC
Site Address 3103 W CRESCENT RIM DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: Wire new home
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final5/5/20175/8/20175/8/2017APASS
DetailsEric Story
Phone #: ###-#### Inspection requested via web by mike brown
Corrections fixed final ok
Final5/5/20175/5/20175/5/2017PFAIL
DetailsTom Saunders
Rick Phone #: ###-#### Inspection requested via web by mike brown...


1...closet switch off hallway installed upside down

2...open neutral in outlet in office

3...back patio outlets not working..GFI will not set

4..lights not working through out house..stairwell, upstairs landing, etc.

5..GFI protection of unfinished portions of basement...210.8(A)(5)


Rough-In Permanent Service9/13/20169/13/20169/13/2016PPASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Eric Brown

rough in ok to cover
p/s u/g n ok
Issue PAID IN FULL permit  9/13/2016 DONE
Payment received via Govolutions
Application received  9/13/2016 DONE
This permit was created on the web by Eric Brown