Final | 12/28/2016 | 12/29/2016 | 12/29/2016 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by TOM BICANDI....
corrections made...ok to final
|
Final | 12/26/2016 | 12/27/2016 | 12/27/2016 | A | FAIL |
Tom Saunders
|
|
|
Door code 0152 Phone #: ###-#### Inspection requested via web by TOM BICANDI
1) available fault current label on service needed
2) intersystem bond needs added at service
3) light not installed in mop/water heater closet
4) front office light switch in upside down
5) outlet under bath sink has no power
6) hall switch below thermostat does not operate anything...no electrical plans on site for verification
|
Rough-In Permanent Service | 9/21/2016 | 9/22/2016 | 9/22/2016 | A | PASS |
Tom Saunders
|
|
|
Door access code is 0152 Phone #: ###-#### Inspection requested via web by TOM BICANDI
check final intersystem bond and AFC rough in ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 9/21/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/21/2016 | | DONE |
|
|
|
This permit was created on the web by TOM BICANDI
|
First Notice | 12/29/2016 | 12/29/2016 | | | |
Tom Saunders
|
|
|
|