Final | 12/7/2016 | 12/8/2016 | 12/8/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kyle Lott Final ok
|
Final | 12/6/2016 | 12/7/2016 | 12/7/2016 | P | PART |
Rock A. Hudson
|
|
|
Please call Kyle for any questions or concerns. Phone #: ###-#### Inspection requested via web by Kyle Lott 210.8- Receptacle near furnace to left of stair with in 6' of sink shall have GFCI protection. 314.23- Boxes shall be securely mounted. ceiling in front of stair and niche by ramp. 358.30- EMT shall be secured with in 3' of a box. room in front of stair. 406.6- Receptacles mounted to face plate shall cover box completely. Cover not secured to box in room to far right of stair. Contractor to repair today. TCO ok
|
Electrical Rough-In | 9/29/2016 | 9/29/2016 | 9/29/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Kyle Lott Wall rough in ok cover
|
Final | 9/27/2016 | 9/28/2016 | 9/28/2016 | A | CANC |
Rock A. Hudson
|
|
|
Concrete electrode Phone #: ###-#### >> Inspection requested via web by Kyle Lott Inspection cancelled from web by: Kyle Lott
|
Electrical Rough-In | 9/26/2016 | 9/27/2016 | 9/27/2016 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kyle Lott 330.12 Subject to physical damage. ( MC cable stapped to the inside channel of metals studs throughout remodel)
|
Issue PAID IN FULL permit | | | 9/26/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 9/26/2016 | | DONE |
|
|
|
This permit was created on the web by Kyle Lott
|
First Notice | 12/8/2016 | 12/8/2016 | | | |
Rock A. Hudson
|
|
|
|