Permit Information
Permit NumberELE16-03325
StatusFinaled
Name BAR XL
Site Address 2037 S LONGMONT AVE
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: new construction complete wiring
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final2/3/20172/3/20172/3/2017APASS
DetailsJames Ady
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks final ok
Final1/31/20171/31/20171/31/2017PFAIL
DetailsJames Ady
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks 210.52.C 1 Recep shall be installed within 24in of cook top 230.70. Each structure shall have disc. mean ( Detached garage) 314.20 Boxes set back more than1/4in shall have extension rings. (all weather proof, mirrors and Up stair 2gang for wall sconce.) 422.30 Furnace shall have Disc means. 334.12 B4 NM cable shall not be installed in wet location 300.9 the inside of an above ground conduit shall be considered a wet location (NM cable going to A/C disconnect)
Rough-In Permanent Service10/12/201610/12/201610/12/2016PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Jason Wicks rough in ok p/s u/g n ok
Issue PAID IN FULL permit  10/12/2016 DONE
Payment received via Govolutions
Application received  10/12/2016 DONE
This permit was created on the web by Jason Wicks