Final | 12/19/2016 | 12/20/2016 | 12/20/2016 | A | PASS |
James Ady
|
|
|
Garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
|
Electrical Rough-In | 10/24/2016 | 10/25/2016 | 10/25/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis Rough in ok cover
|
Permanent Service | 10/25/2016 | 10/25/2016 | 10/25/2016 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis p/s u/g n ok
|
Electrical Rough-In | 10/21/2016 | 10/24/2016 | 10/24/2016 | A | FAIL |
Rock A. Hudson
|
|
|
Will call Monday to fix application price on permit. Phone #: ###-#### Inspection requested via web by Charles Davis 110.3- Service riser shall be installed as per manufacterers instructions. Shall provide for rise and fall of conduit. 110.12(B)- Service riser coupling broken. 300.4- Nail plates shall protect NM cable where hole does not maintain 1 1/4" from framing surface. 45 degree corners and others. 300.15- Can over vanity secure cover on junction box. 334.12- NM cable shall not be installed where subject to physical damage. Hangs below truss in garage.
|
Issue PAID IN FULL permit | | | 10/20/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/20/2016 | | DONE |
|
|
|
This permit was created on the web by Charles Davis
|