Final | 2/9/2017 | 2/9/2017 | 2/9/2017 | A | PASS |
Rock A. Hudson
|
|
|
Garage code 1414. Thank you Phone #: ###-#### Inspection requested via web by daniel bibikov Final ok
|
Final | 2/8/2017 | 2/8/2017 | 2/8/2017 | P | FAIL |
Rock A. Hudson
|
|
|
garage code 1414. thank you Phone #: ###-#### Inspection requested via web by daniel bibikov 110.3- Outdoor receptacle outlets will not work. 1 front 1 rear. 200.7- White conductors used as ungrounded conductors shall be identified as other than white or neutral gray. 334.80- Max overcurrent device for 6-3 NM cable shall be sized to 60 degree column. 55 amp max 60 installed.
|
Rough-In Permanent Service | 10/26/2016 | 10/26/2016 | 10/26/2016 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s o/h n ok
|
Issue PAID IN FULL permit | | | 10/25/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/25/2016 | | DONE |
|
|
|
This permit was created on the web by daniel bibikov
|