Final | 2/27/2017 | 2/28/2017 | 2/28/2017 | A | PASS |
Eric Story
|
|
|
Wes Phone #: ###-#### Final for small kitchen remodel ok
|
Electrical Rough-In | 10/27/2016 | 10/27/2016 | 10/27/2016 | P | PASS |
Mark Moncarr
|
|
|
Wesley Phone #: ###-#### Corrections made, ok cover
|
Electrical Rough-In | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | FAIL |
Rock A. Hudson
|
|
|
Wesley Phone #: ###-#### 210.52- Kitchen counter top area shall not be more than 24" from a receptacle area. Peninsula receptacle shall be located at end of counter with in 12" of counter top and not more than 6" under overhang. 310.15- Wiring required for 20 amp receptacle outlets shall be 12 guage, 14-2 installed.
|
Conference | 10/26/2016 | 10/26/2016 | 10/26/2016 | P | DONE |
Rock A. Hudson
|
|
|
Wesley Phone #: ###-#### Discussed requirements for receptacles in east wall kitchen remodel. All receptacle outlets serving counter top areas shall be on 20 amp circuit, tamper resistant and GFCI protected. Peninsula receptacle shall be with in 12" vertical of counter top and not more than 6" under overhang also not point on counter top surface shall be more than 24" from receptacle.
|
Application received | | | 10/26/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 10/26/2016 | | DONE |
|
|
|
|