Final | 12/30/2016 | 1/3/2017 | 1/3/2017 | A | PASS |
Rock A. Hudson
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis Final ok
|
Final | 12/29/2016 | 12/30/2016 | 12/30/2016 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis 110.25- Dishwasher shall have a disconnecting means as per 422.30 lock out acceptable. 440.6- AC overcurrent device shall not exceed nameplate rating. 30 amp on 25 amp max.
|
Electrical Rough-In | 10/31/2016 | 10/31/2016 | 10/31/2016 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis Rough in ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 10/31/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 10/31/2016 | | DONE |
|
|
|
This permit was created on the web by Charles Davis
|