Final | 1/29/2017 | 1/30/2017 | 1/30/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray....
corrections made...ok to final
|
Final | 1/27/2017 | 1/27/2017 | 1/27/2017 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Murray Inspection cancelled from web by: Robert Murray
|
Final | 1/12/2017 | 1/13/2017 | 1/13/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Code to get in 3162 Phone #: ###-#### Inspection requested via web by Robert Murray 110.3- Garage circuit not complete. Opener receptacle still temp receptacle installed. GFI works other do not. 210.52-Receptacles located in cabinets do not count for general receptacle layout. Add receptacles on each side of entertainment cabinet 24" or greater walls. 356.30- Flexible non metallic conduit installed in island shall be secured with in 12" of a box and 6' intervals. 410.16- Master closet luminaire has standard screw shall with LED lamp shall have 12" clearance from storage shelf.
|
Final | 1/9/2017 | 1/10/2017 | 1/10/2017 | P | CANC |
Tom Saunders
|
|
|
Code to get in 3162 Phone #: ###-#### >> Inspection requested via web by Robert Murray Inspection cancelled from web by: Robert Murray
|
Final | 1/8/2017 | 1/9/2017 | 1/9/2017 | P | CANC |
Tom Saunders
|
|
|
Phone #: ###-#### >> Inspection requested via web by Robert Murray Inspection cancelled from web by: Robert Murray
|
Rough-In Permanent Service | 11/2/2016 | 11/3/2016 | 11/3/2016 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Robert Murray...
rough in ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 11/2/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/2/2016 | | DONE |
|
|
|
This permit was created on the web by Robert Murray
|