Temporary Service | 11/9/2016 | 11/9/2016 | 11/9/2016 | P | PASS |
James Ady
|
|
|
Any questions please let me know, ###-####, thx, TW Phone #: ###-#### Inspection requested via web by Stephen Kren t/s o/h n ok
|
Issue PAID IN FULL permit | | | 11/9/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 11/9/2016 | | DONE |
|
|
|
This permit was created on the web by Stephen Kren
|
First Notice | 11/9/2016 | 11/9/2016 | | | |
James Ady
|
|
|
|