Permit Information
Permit NumberELE16-03673
StatusFinaled
Name RUMMER ELECTRIC
Site Address 3353 E WINDSONG DR
Project Name 
Customer Number511
ePlanReviewNo
Description
Complete Installation (includes room count and per
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final4/14/20174/14/20174/14/2017PPASS
DetailsJames Ady
Phone #: ###-#### Inspection requested via web by Neal Rumsey final ok
Rough-In Permanent Service11/15/201611/16/201611/16/2016APASS
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
BLD to check soffits. Contractor stated all is where it needs to be with other questions. Rough in ok cover p/s u/g n ok
Rough-In Permanent Service11/14/201611/14/201611/14/2016PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
110.3- Service feeders not installed.
210.52(A)- Receptacle outlet shall be installed for 6' wall space to right of fireplace.
210.52(B)- Pantry counter top shall have receptacle outlet layout same as kitchen.
210.52(D)- Master bath vanity receptacle is placed behind wall and will ot be in place to serve basin.
250.110- Equipment ground shall be connected in temp connection of furnaces and abrasion protection shall be present as per 300.4.
IBC- Boxes for soffit cans shall be down to soffit material for air seal.
590.6- 50 amp GFCI receptacle in temp pole will not trip.
Final11/10/201611/14/201611/14/2016ACANC
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by Neal Rumsey
Needed rough in and permanant service.
Issue PAID IN FULL permit  11/10/2016 DONE
Payment received via Govolutions
Application received  11/10/2016 DONE
This permit was created on the web by Neal Rumsey