Final | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | PASS |
Rock A. Hudson
|
|
|
All complete, signed off in office. Final ok
|
Final | 2/23/2018 | 2/26/2018 | 2/26/2018 | A | PART |
Rock A. Hudson
|
|
|
Units 310,410, 510, 610 ; 710 Courtyard 3rd level and Rooftop Contact Bob Mott Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Roof top and level 3 patio on core and shell permit, made notes on that permit. 310, 410, 414, 510, 610, 710 signed off in office. TCO OK
|
Final | 2/9/2018 | 2/12/2018 | 2/12/2018 | A | PART |
Rock A. Hudson
|
|
|
Room 334 Contact Bob Mott Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office. TCO ok
|
Final | 2/8/2018 | 2/9/2018 | 2/9/2018 | A | PART |
Rock A. Hudson
|
|
|
Rms 421 ; 422 Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 421, 422, 434 signed off in office, TCO ok
|
Final | 2/8/2018 | 2/8/2018 | 2/8/2018 | P | PART |
Rock A. Hudson
|
|
|
Unit # 321 and East side corridor Contact Bob Mott prior to 3:15 Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 3 321 and east side corridor signed of in office. TCO ok
|
Final | 2/2/2018 | 2/5/2018 | 2/5/2018 | A | PART |
Rock A. Hudson
|
|
|
East corridor 4th Floor final inspection Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted signed off in office. Level 4 east corridor TCO ok
|
Final | 2/2/2018 | 2/2/2018 | 2/2/2018 | P | PART |
Rock A. Hudson
|
|
|
Bob Mott ###-####. 301, 302, 304 thru 309, 311 thru 320, and 322. Heat tape located on patio area need installed. Rooms noted signed off in office. TCO ok
|
Conference | 1/31/2018 | 1/31/2018 | 1/31/2018 | P | DONE |
Rock A. Hudson
|
|
|
East building 3 thru 7- 701 thru 709, 711 thru 722,734, corridor. 601 thru 609, 611 thru 622, 634, corridor. 501 thru 509, 511 thru 522, 534, corridor. 401 thru 409, 411, 412, 413, 415 thru 422, 434. Stairways 1 and 2 ok. All levels no rooms with 03. All level room 10 not ready. 414 NR due to water damage. Level 4 corridors not ready. Level 3 no final inspections as of 1-31-18.
|
Final | 1/29/2018 | 1/29/2018 | 1/29/2018 | P | PART |
Rock A. Hudson
|
|
|
units 401,402,404 through 409, 411, 412,413, 415-420 Phone #: ###-#### Inspection requested via web by Cathy Duchek 410 NR, 414 water damage, 401, 402, 404 thru 409, 411, 412, 413, 415 thru 420 and 434 and 534, 538 All signed off in office TCO as noted ok
|
Final | 1/19/2018 | 1/19/2018 | 1/19/2018 | A | PART |
Rock A. Hudson
|
|
|
corridor 5th floor, units 401, 402, 404,405,406 Phone #: ###-#### Inspection requested via web by Cathy Duchek 405 bath back splash not in, other areas noted signed off in office. Partial final ok
|
Final | 1/18/2018 | 1/18/2018 | 1/18/2018 | A | PART |
Rock A. Hudson
|
|
|
final units 521,522 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office. Partial final ok
|
Final | 1/17/2018 | 1/17/2018 | 1/17/2018 | A | PART |
Rock A. Hudson
|
|
|
Final on units 501, 502, 504 through 520 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office. Partial final ok
|
Final | 1/11/2018 | 1/12/2018 | 1/12/2018 | A | PART |
Rock A. Hudson
|
|
|
6th and 7th floor corridors, stair 1, stair 2 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted signed off in office. Temp final ok
|
Final | 1/9/2018 | 1/9/2018 | 1/9/2018 | A | PART |
Rock A. Hudson
|
|
|
units 701,702,704 through 709, 721,722 Phone #: ###-#### Inspection requested via web by Cathy Duchek Added 711, 712, 713 to list of rooms, Units signed off in office. Partial final ok.
|
Final | 1/6/2018 | 1/8/2018 | 1/8/2018 | A | PART |
Rock A. Hudson
|
|
|
units 714-720 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted and signed off in office partial final ok
|
Final | 1/4/2018 | 1/4/2018 | 1/4/2018 | P | PART |
James Ady
|
|
|
units 601,602,621,622, 604 through 606 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms listed final ok
|
Final | 1/2/2018 | 1/2/2018 | 1/4/2018 | P | PART |
Daryl DeGrange
|
|
|
Final inspections units 611 through 620, finals units 607, 608, and 609 Phone #: ###-#### Inspection requested via web by Cathy Duchek Partial final ok for units listed
|
Electrical Rough-In | 12/11/2017 | 12/12/2017 | 12/12/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids in community room #321 Phone #: ###-#### Inspection requested via web by Cathy Duchek Noted on contractor print rough in ok cover
|
Electrical Rough-In | 11/15/2017 | 11/15/2017 | 11/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
Dropped lids in Elevator Lobbies 333, 433,533,633,733 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted signed off in office drop lids. Rough in ok cover
|
Electrical Rough-In | 10/10/2017 | 10/10/2017 | 10/10/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids in units 301, 302, 304, 306, 308, 310, 312, 314, 316, 318, 320, 322. corridors 3rd floor Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted hardlids rough in ok cover
|
Electrical Rough-In | 9/29/2017 | 10/6/2017 | 10/6/2017 | A | PASS |
Eric Story
|
|
|
dropped lids units 305,307,309,311,313,315, 317, 319 Phone #: ###-#### Inspection requested via web by Cathy Duchek Odd units 305 thru 319 dropped hard lid ceilings in entry and baths ok to cover
|
Electrical Rough-In | 9/27/2017 | 9/27/2017 | 9/27/2017 | A | PASS |
Daryl DeGrange
|
|
|
corridor 435b,435a,436a,535b,535a,536a,units 421,units 422 dropped lids Phone #: ###-#### Inspection requested via web by Cathy Duchek Drop lids Rough-in ok
|
Electrical Rough-In | 9/18/2017 | 9/19/2017 | 9/19/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids in units 401,402, 404 through 420 Phone #: ###-#### Inspection requested via web by Cathy Duchek 421, 422 not ready, units noted signed off in office. Rough in ok cover
|
Electrical Rough-In | 9/13/2017 | 9/13/2017 | 9/13/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 601,602, 604 through 620 Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted completed 8-24-17. Actual units 501, 502, 504 thru 522 signed off in office. Droplid rough in ok cover
|
Electrical Rough-In | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Rock A. Hudson
|
|
|
unit 321 rough-in Phone #: ###-#### Inspection requested via web by Cathy Duchek Room noted signed off in office. Rough in ok cover
|
Electrical Rough-In | 8/28/2017 | 8/29/2017 | 8/29/2017 | A | NR |
Daryl DeGrange
|
|
|
units 320,321 Phone #: ###-#### Inspection requested via web by Cathy Duchek 321 Not ready at this time.
|
Electrical Rough-In | 8/29/2017 | 8/29/2017 | 8/29/2017 | P | PASS |
Daryl DeGrange
|
|
|
units 320,318 Phone #: ###-#### Inspection requested via web by Cathy Duchek R/I ok cover
|
Electrical Rough-In | 8/25/2017 | 8/25/2017 | 8/25/2017 | P | PASS |
Rock A. Hudson
|
|
|
dropped lids units 701,702,704-722 corridors 735A and 735B, units 310,312,314 Phone #: ###-#### Inspection requested via web by Cathy Duchek Last light in 735(A) and 722 not ready rest signed off in office. Areas noted rough in ok cover
|
Electrical Rough-In | 8/24/2017 | 8/24/2017 | 8/24/2017 | A | PASS |
Rock A. Hudson
|
|
|
Dropped ceilings in units 601,602,604 through 622, corridor 635A,635B Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted and signed off in office rough in ok cover
|
Electrical Rough-In | 8/18/2017 | 8/18/2017 | 8/18/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 306, units 308 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rough in ok cover
|
Electrical Rough-In | 8/17/2017 | 8/17/2017 | 8/17/2017 | A | PASS |
Rock A. Hudson
|
|
|
units 322, unit 305 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office rough in ok cover
|
Electrical Rough-In | 8/15/2017 | 8/15/2017 | 8/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 301, 302, 304, 305, 307, 309 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted in office rough in ok cover
|
Electrical Rough-In | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | PASS |
Rock A. Hudson
|
|
|
utility rooms 338 through 638 Phone #: ###-#### Inspection requested via web by Cathy Duchek Utility rooms 334 thru 634 as noted in office rough in ok cover
|
Electrical Rough-In | 8/2/2017 | 8/3/2017 | 8/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
Shaft in utility rooms, units 406, 319,317,315, 313, and 311 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted with data walls in utility rooms on floors 3 thru 7 noted in office print and unit logs. Rough in ok cover
|
Electrical Rough-In | 7/25/2017 | 7/26/2017 | 7/26/2017 | P | PART |
Rock A. Hudson
|
|
|
utility 734 ceiling, units 401,402,404 through 414, 421,422 Phone #: ###-#### Inspection requested via web by Cathy Duchek All list except 406 due to no access to all walls because full of insulation. 615 has receptacle in bedroom 6'6" from door OK with location. All other listed and signed off in inspection book in office. Rough in noted ok cover
|
Electrical Rough-In | 7/24/2017 | 7/24/2017 | 7/24/2017 | P | PASS |
Rock A. Hudson
|
|
|
utility 734, shaft wall units 305-705 Phone #: ###-#### Inspection requested via web by Cathy Duchek 305 thru 705 duct shaft and utility 734 walls. Areas noted on inspection print rough in ok cover
|
Electrical Rough-In | 7/19/2017 | 7/20/2017 | 7/20/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 415 through 420, utility 734 Phone #: ###-#### Inspection requested via web by Cathy Duchek 734 not ready. 415 thru 420 units rough in ok cover
|
Electrical Rough-In | 7/18/2017 | 7/18/2017 | 7/18/2017 | P | PASS |
Rock A. Hudson
|
|
|
rough-in stairwell 1, stairwell 2 Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted on inspection print in office stair 1, 2 rough in ok cover
|
Electrical Rough-In | 6/30/2017 | 6/30/2017 | 6/30/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 501,502,504 thru 509, 521,522 Phone #: ###-#### Inspection requested via web by Cathy Duchek 704 and rooms noted signed off in office rough in ok cover
|
Electrical Rough-In | 6/29/2017 | 6/29/2017 | 6/29/2017 | P | PASS |
Mark Moncarr
|
|
|
units 510 thru 520, elevator shaft Phone #: ###-#### Inspection requested via web by Cathy Duchek Ok cover. 7th floor elevator shaft with conduit stubs for related equiptment. Rooms 510-520 ok.
|
Electrical Rough-In | 6/7/2017 | 6/8/2017 | 6/8/2017 | A | PASS |
Rock A. Hudson
|
|
|
unit 704, unit 722 Phone #: ###-#### Inspection requested via web by Cathy Duchek Noted in office, units noted rough in ok cover
|
Electrical Rough-In | 6/6/2017 | 6/7/2017 | 6/7/2017 | P | PART |
Rock A. Hudson
|
|
|
units 701,702,704,705,706, corridor 735A,;735B Phone #: ###-#### Inspection requested via web by Cathy Duchek 704 not ready rest noted on office sheets. Rough in ok cover
|
Electrical Rough-In | 6/1/2017 | 6/1/2017 | 6/1/2017 | P | PASS |
Rock A. Hudson
|
|
|
coriidors 437A, 437B, 437c Phone #: ###-#### Inspection requested via web by Cathy Duchek To clarify ELE16-00580 poduim, ELE16-03933 core and shell, ELE16-03932 west fowler, ELE16-03931 east fowler. ELE17-01627 Rex pizza with different address. Firelid for 437 A, B, C rough in ok cover
|
Electrical Rough-In | 5/26/2017 | 5/30/2017 | 5/30/2017 | A | PASS |
Eric Story
|
|
|
units in 7th floor. units 708 thru 722. Phone #: ###-#### Inspection requested via web by Cathy Duchek 7th floor units 707 thru 720 and noted on inspection record ok cover walls and ceilings
|
Electrical Rough-In | 5/23/2017 | 5/23/2017 | 5/23/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 608-622 corridors 537A, 537B, 537C Phone #: ###-#### Inspection requested via web by Cathy Duchek Book located in general contractors job trailer to sign off on inspections. 601, 602, 604 thru 608 and 621, 622 and firelids for corridors noted rough in ok cover
|
Electrical Rough-In | 5/22/2017 | 5/22/2017 | 5/22/2017 | P | PASS |
Rock A. Hudson
|
|
|
Units 609-620 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted marked on contractor print firelids included rough in ok cover.
|
Electrical Rough-In | 5/9/2017 | 5/10/2017 | 5/10/2017 | P | PASS |
Rock A. Hudson
|
|
|
ceiling rough-in 3rd floor corridors 335B, 335A, 336A. Phone #: ###-#### Inspection requested via web by Cathy Duchek Different floor 635 A and B, 636 A firelid rough in ok cover. Discussed peninsula area for kitchen counters receptacles. One additional on wall where peninsula attched.
|
Conference | 2/14/2017 | 2/15/2017 | 2/15/2017 | A | DONE |
Rock A. Hudson
|
|
|
Lonny Phone #: ###-#### Discussed the installation of NM cable areas, receptacle locations in dwellings, voltage drop of unit feeders. NM cable shall be permitted in all areas of 3, 4, 5, construction above level 2. Corridors ok and all penetrations in firewalls and ceilings shall be sealed before electrical inspections. Receptacle locations on print inside entry door not a hallway or habitable room so recepts can be removed if desired. ADA rooms shall have all operating handles of over current devices at or below 48".
|
Issue PAID IN FULL permit | | | 12/5/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/5/2016 | | DONE |
|
|
|
This permit was created on the web by Cathy Duchek
|
First Notice | 2/28/2018 | 2/28/2018 | | | |
Rock A. Hudson
|
|
|
|