Final | 2/28/2018 | 2/28/2018 | 2/28/2018 | P | PASS |
Rock A. Hudson
|
|
|
All complete, signed off in office. Final ok
|
Final | 2/23/2018 | 2/26/2018 | 2/26/2018 | A | PART |
Rock A. Hudson
|
|
|
Courtyard 3rd level and Rooftop Contact Bob Mott Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Roof top on core and shell permit ELE16-03933. Made notes on that permit.
|
Final | 2/9/2018 | 2/12/2018 | 2/12/2018 | A | PART |
Rock A. Hudson
|
|
|
Rms 323-332 Contact Bob Mott Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted and 338 signed off in office. TCO ok
|
Final | 2/8/2018 | 2/9/2018 | 2/9/2018 | A | PART |
Rock A. Hudson
|
|
|
Final for Rooms 423 through 434 Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek 423 thru 432 and 438 signed off in office TCO ok
|
Final | 2/8/2018 | 2/8/2018 | 2/8/2018 | P | PART |
Rock A. Hudson
|
|
|
West side corridor Electrician on site until 3:15 Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 3 west side corridor signed off in office. TCO ok
|
Final | 2/2/2018 | 2/5/2018 | 2/5/2018 | A | PART |
Rock A. Hudson
|
|
|
West Corridor 4th Floor final inspection Contact Bob Mott Thank you Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted signed off in office. Level 4 west corridor TCO ok.
|
Conference | 1/31/2018 | 1/31/2018 | 1/31/2018 | P | DONE |
Rock A. Hudson
|
|
|
Levels 3 thru 7 west of building. 723 thru 732, 738, corridor. 623 thru 632, 638, corridor. 523 thru 532, 538, corridor. Stairways 3 and 4. No final inspections on levels 3 and 4.
|
Final | 1/19/2018 | 1/19/2018 | 1/19/2018 | A | PART |
Rock A. Hudson
|
|
|
corridor on 5th floor Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted signed off in office. Partial final ok
|
Final | 1/18/2018 | 1/18/2018 | 1/18/2018 | A | PART |
Rock A. Hudson
|
|
|
final units 523-532 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office. Partial final ok
|
Final | 1/11/2018 | 1/12/2018 | 1/12/2018 | A | PART |
Rock A. Hudson
|
|
|
corridors 6th and 7th floor, stair 3, stair 4 Phone #: ###-#### Inspection requested via web by Cathy Duchek Receptacle at bottom of stair 4 check next trip. Areas noted siged off in office. Temp final ok
|
Final | 1/9/2018 | 1/10/2018 | 1/10/2018 | A | PART |
Rock A. Hudson
|
|
|
units 723 through 732, Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office, Partial final ok
|
Final | 1/9/2018 | 1/9/2018 | 1/9/2018 | A | PART |
Rock A. Hudson
|
|
|
units 624, 630 Phone #: ###-#### Inspection requested via web by Cathy Duchek Corrections complete 624 water heater and 630 bath GFI Partial final ok
|
Final | 1/4/2018 | 1/4/2018 | 1/4/2018 | P | PART |
James Ady
|
|
|
units 623-632 Phone #: ###-#### Inspection requested via web by Cathy Duchek rooms listed only final ok
|
Electrical Rough-In | 11/15/2017 | 11/15/2017 | 11/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
Thrash rooms dropped ceilings 338,438,538,638,738 Phone #: ###-#### Inspection requested via web by Cathy Duchek Areas noted trash rooms drop lids signed off in office. Rough in ok cover
|
Electrical Rough-In | 9/29/2017 | 10/4/2017 | 10/4/2017 | A | PASS |
Daryl DeGrange
|
|
|
dropped lids units 323 through 332 and parking garage lobby hard lid Phone #: ###-#### Inspection requested via web by Cathy Duchek
|
Electrical Rough-In | 9/27/2017 | 9/27/2017 | 9/27/2017 | A | PASS |
Daryl DeGrange
|
|
|
corridors 437C, 437B, 436B, 537C,537B, 536B dropped lids Phone #: ###-#### Inspection requested via web by Cathy Duchek Drop lids including 5A Rough-in ok cover
|
Electrical Rough-In | 9/18/2017 | 9/19/2017 | 9/19/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids units 423-432 Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. Rough in ok cover
|
Electrical Rough-In | 9/14/2017 | 9/14/2017 | 9/14/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids in units 523 through 532 Phone #: ###-#### Inspection requested via web by Cathy Duchek Units noted signed off in office. Drop lids rough in ok cover
|
Electrical Rough-In | 9/13/2017 | 9/13/2017 | 9/13/2017 | P | CANC |
Rock A. Hudson
|
|
|
units 623 through 632 dropped ceilings Phone #: ###-#### Inspection requested via web by Cathy Duchek See rough in 9-12-17 for these units
|
Electrical Rough-In | 9/11/2017 | 9/12/2017 | 9/12/2017 | A | PASS |
Rock A. Hudson
|
|
|
Corridors 637A, 636b Phone #: ###-#### Inspection requested via web by Cathy Duchek Added hardlids in units 623 thru 632. Areas noted signed off in office. Hardlids for areas noted rough in ok cover
|
Electrical Rough-In | 9/8/2017 | 9/8/2017 | 9/8/2017 | A | PASS |
Rock A. Hudson
|
|
|
dropped lids units 723-725, units 728-732 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed off in office. Rough in ok cover
|
Electrical Rough-In | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Rock A. Hudson
|
|
|
dropped ceilings in units 726, 727 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted droplids signed off in office. Rough in ok cover
|
Electrical Rough-In | 8/8/2017 | 8/8/2017 | 8/8/2017 | P | PASS |
Rock A. Hudson
|
|
|
trash rooms 338 through 738 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted in office and above rough in ok cover
|
Electrical Rough-In | 7/18/2017 | 7/18/2017 | 7/18/2017 | P | PASS |
Rock A. Hudson
|
|
|
Electrical rough-in stairwell 3, stairwell 4 Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted in office on inspection print stair 3, 4 rough in ok cover
|
Electrical Rough-In | 6/27/2017 | 6/27/2017 | 6/27/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 323 thru 332 Phone #: ###-#### Inspection requested via web by Cathy Duchek
Rooms noted sign off in office rough in ok cover
|
Electrical Rough-In | 6/21/2017 | 6/22/2017 | 6/22/2017 | A | PASS |
Rock A. Hudson
|
|
|
rough-in units 423 through 432 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted signed of in office rough in ok cover
|
Electrical Rough-In | 6/20/2017 | 6/20/2017 | 6/20/2017 | P | PASS |
Rock A. Hudson
|
|
|
units 523 thru 532 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted and signed in office rough in ok cover
|
Electrical Rough-In | 6/13/2017 | 6/15/2017 | 6/15/2017 | A | PASS |
Rock A. Hudson
|
|
|
6th floor area ''B'' electrical rough-in rooms: 623, 624, 625, 626, 627, 628, 629, 630, 631, ; 632. Call Lonny when on site. Thanks. Phone #: ###-#### Inspection requested via web by Lonny Baum Rooms noted and marked in office book and 3rd floor corridor (A) fire lid rough in ok cover
|
Electrical Rough-In | 6/13/2017 | 6/14/2017 | 6/14/2017 | A | PASS |
Rock A. Hudson
|
|
|
3rd area ''B'' west corridor rough-in. Call Lonny when on-site, thanks Phone #: ###-#### Inspection requested via web by Lonny Baum 3rd floor corridor (B) and 1st floor liveworks 2' east wall rough in ok cover.
|
Electrical Rough-In | 6/7/2017 | 6/8/2017 | 6/8/2017 | A | PASS |
Rock A. Hudson
|
|
|
unit 724 Phone #: ###-#### Inspection requested via web by Cathy Duchek Noted in office, unit noted rough in ok cover
|
Electrical Rough-In | 6/6/2017 | 6/7/2017 | 6/7/2017 | P | PASS |
Rock A. Hudson
|
|
|
Units 721,723,725,726,727,728,729,730,731,732 Phone #: ###-#### Inspection requested via web by Cathy Duchek Rooms noted and marked in office rough in ok cover
|
Electrical Rough-In | 5/12/2017 | 5/15/2017 | 5/15/2017 | P | PASS |
Rock A. Hudson
|
|
|
corridors 637A, 637B, 637C fire lid on 6th floor. Fabian Luna Phone #: ###-#### Inspection requested via web by Cathy Duchek Area noted and marked on contractor print. Fire lid rough in ok cover
|
Issue PAID IN FULL permit | | | 12/5/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/5/2016 | | DONE |
|
|
|
This permit was created on the web by Cathy Duchek
|
First Notice | 2/28/2018 | 2/28/2018 | | | |
Rock A. Hudson
|
|
|
|