Final | 2/1/2017 | 2/2/2017 | 2/2/2017 | A | PASS |
Tom Saunders
|
|
|
code 1234 Phone #: ###-#### Inspection requested via web by Bob Glenn...
ok to final
|
Rough-In Permanent Service | 12/16/2016 | 12/19/2016 | 12/19/2016 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn.....
rough ok to cover p/s u/g n ok
|
Issue PAID IN FULL permit | | | 12/8/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/8/2016 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|