Final | 2/8/2017 | 2/10/2017 | 2/10/2017 | P | PASS |
Mark Moncarr
|
|
|
Call half hour before // John Phone #: ###-#### Corrections made. Ok final
|
Final | 1/27/2017 | 1/30/2017 | 1/30/2017 | P | FAIL |
Rock A. Hudson
|
|
|
would like call ahead Phone #: ###-#### Homeowner took over complete trim out of work shop. No conference requested. 210.8- GFCI receptacles shall be located in readily accessible locations. To move GFCI behind refrigerator to over counter. 210.8(A)(3)- Back receptacle located in 2 gang and front receptacles not GFCI protected, they shall be. 210.52(B)(2)- Small appliance circuit shall not feed outdoor receptacles. 230.70- A means shall be provided to disconnect all conductors from a structure. Need main disconnect for work shop. 406.9- Outdoor receptacles exposed to weather shall have heavy duty in use cover installed. Front. 406.9(B)- Front outdoor receptacle shall be tamper and weather resistant type. 406.9 ex.- Receptacles located above 5'5" not required to be temper resistant type. Microwave. 406.12- Tamper resistant receptacles shall be installed through out work shop.
|
Application received | | | 12/27/2016 | | |
|
|
|
|
Issue PAID IN FULL permit | | | 12/27/2016 | | DONE |
|
|
|
|