Final | 4/26/2017 | 4/27/2017 | 4/27/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine Corrections made final ok
|
Final | 4/25/2017 | 4/26/2017 | 4/26/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine 250.94- Intersystem bond shall be installed.
352.30- Service riser shall be secured with in 3' of meter.
410.10- Bulb installed above shower shall be listed for wet locations. Unable to verify. Provide documentation or change to listed lamp.
|
Final | 4/24/2017 | 4/25/2017 | 4/25/2017 | P | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine missing lights, bed receps dead,still bugging house.
|
Rough-In Permanent Service | 1/5/2017 | 1/6/2017 | 1/6/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine rough in ok to cover p/s u/g n ok
|
Rough-In Permanent Service | 1/4/2017 | 1/5/2017 | 1/5/2017 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by danny perrine Canceled Unable to make, To much snow. Gave verbal ok to foam seal
|
Rough-In Permanent Service | 1/3/2017 | 1/5/2017 | 1/4/2017 | A | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by danny perrine Inspection cancelled from web by: danny perrine
|
Issue PAID IN FULL permit | | | 12/28/2016 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 12/28/2016 | | DONE |
|
|
|
This permit was created on the web by danny perrine
|