Information based on query as of Wednesday, July 17, 2024.
Permit Information
Permit NumberELE17-00009
StatusIssued
Name KOHLER MELISSA L
Site Address 13477 W BLUEBONNET DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Homeowner Online - Addition: Adding a dining room and expanding the master bedroom.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
ELE-Aging Inspection6/5/20206/5/20206/5/2020 DONE
DetailsDaryl DeGrange
Still under construction
ELE-Aging Inspection2/26/20202/26/20202/26/2020 DONE
DetailsTom Saunders
waiting on homeowner
ELE-Aging Inspection11/27/201911/27/201911/27/2019 DONE
DetailsTom Saunders
still under construction
ELE-Aging Inspection8/28/20198/28/20198/28/2019 DONE
DetailsTom Saunders
waiting on homeowner/permit holder
Final5/29/20195/31/20195/31/2019ANR
DetailsMark Moncarr
Ryan Phone #: ###-####
ELE-Aging Inspection3/29/20193/29/20193/29/2019 PASS
DetailsTom Saunders
extended permit
ELE-Request for Extension3/29/20193/29/20193/29/2019PPASS
DetailsTom Saunders
spoke with permit holder...extension requested...still under construction
Electrical Rough-In8/7/20178/8/20178/8/2017APASS
DetailsTom Saunders
Phone #: ###-#### Inspection requested via web by Ryan Kohler....

discussed tamperresistant outlets and arc fault protection for new master....rough in ok to cover
Electrical Rough-In1/12/20171/13/20171/13/2017APASS
DetailsJames Ady
Please call ahead. The house is occupied. Phone #: ###-#### Inspection requested via web by Ryan Kohler Light off master patio is good enough to provide illumination of outdoor entrances to new dining room as per Daryl Degrange. Rough in Dining only ok to cover
Electrical Rough-In1/3/20171/4/20171/4/2017AFAIL
DetailsTom Saunders
Rough inspection for the dining room addition only at this time. Please call prior to inspection. Want to make sure you have access as the home is occupied. Phone #: ###-#### Inspection requested via web by Ryan Kohler...

1..junction box needs sized for number of wires..314.16

2..dining room outlets shall be on 20amp circuit on small appliance circuit..210.52(B)(1)

3...all wallspace 2ft or larger shall have an outlet..210.52(A)(2)
Issue PAID IN FULL permit  1/3/2017 DONE
Payment received via Govolutions
Application received  1/3/2017 DONE
This permit was created on the web by Ryan Kohler