Final | 3/1/2017 | 3/1/2017 | 3/1/2017 | P | PASS |
James Ady
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis corrections made final ok
|
Final | 2/28/2017 | 2/28/2017 | 2/28/2017 | P | FAIL |
James Ady
|
|
|
garage code 1001 Phone #: ###-#### Inspection requested via web by Charles Davis 210.8 A 3 All outdoor receps shall be GFCi protected. ( recep by panel) 110.3 B Listed equipment Shall be installed per man specs. (front WP recep.) 406.9 B 1 Outdoor receps shall be weather resistant.( front WP recep) 334.12 NM cable shall not be exposed. ( romex above range hood)
|
Final | 1/13/2017 | 1/17/2017 | 1/13/2017 | A | CANC |
James Ady
|
|
|
garage code 1001 Phone #: ###-#### >> Inspection requested via web by Charles Davis Inspection cancelled from web by: Charles Davis
|
Rough-In Permanent Service | 1/5/2017 | 1/6/2017 | 1/6/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 1/3/2017 | 1/5/2017 | 1/5/2017 | A | NH |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Charles Davis No access. Too much snow. Foam seal ok No Cover. Recall rough in inspection
|
Issue PAID IN FULL permit | | | 1/3/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/3/2017 | | DONE |
|
|
|
This permit was created on the web by Charles Davis
|