Final | 6/19/2017 | 6/20/2017 | 6/20/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...
corrections made...ok to final
|
Final | 6/7/2017 | 6/8/2017 | 6/8/2017 | P | FAIL |
Tom Saunders
|
|
|
please inspect after 9;30 am Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON
1) available fault current labelling on service 2) outside panels need labelled completely... front and back panels 3) outlet below outside panel shows hot neutral reverse 4) service shall have a intersystem bond bar 5) access to roof units needed to verify labelling, disconnects, breaker size, service outlet, etc. contractor will provide a sturdy ladder or sometime of means for access to roof
|
Final | 5/26/2017 | 5/30/2017 | 5/30/2017 | A | NR |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...
will recall in when ready
|
Final | 4/28/2017 | 5/1/2017 | 5/1/2017 | A | CANC |
Tom Saunders
|
|
|
inspection is for fist storage unit building behind the office Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...
this permit is only associated with office building...contractor has been notified that he must pull a seperate electrical permit for each building and have it associated to each seperate building permit
|
Electrical Rough-In | 2/20/2017 | 2/21/2017 | 2/21/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON...
ok to cover....office space...back storage units connected to this building will still need rough in inspection
|
Electrical Rough-In | 1/18/2017 | 1/19/2017 | 1/19/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON....
discussed with contractor reason for no inspections on underground piping and grounding for srevice...contractor sent 7 pictures...pictures include picture of pipes depth, tape measure verifying, size/type of pipes, length of ground wire and its connections to rebar, pictures can be verified of location with surrounding sceneries, gave warning for all future inspections
|
Permanent Service | 1/19/2017 | 1/19/2017 | 1/19/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by SHAWN TOMLINSON....
p/s u/g n ok
|
Issue PAID IN FULL permit | | | 1/16/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/16/2017 | | DONE |
|
|
|
This permit was created on the web by SHAWN TOMLINSON
|
First Notice | 6/20/2017 | 6/20/2017 | | | |
Tom Saunders
|
|
|
|