Final | 4/7/2017 | 4/10/2017 | 4/10/2017 | A | PASS |
Mark Moncarr
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper Ok final
|
Rough-In Permanent Service | 1/17/2017 | 1/18/2017 | 1/18/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 1/17/2017 | 1/17/2017 | 1/17/2017 | P | FAIL |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by steve cooper....
1) can above sink cannot be wired off small appliance circuit or dishwasher disposal circuit 210.52(B)(2) 422.10
2) where NM cable is used the sheath shall extend not less than 1/4" inside the box 314.17(C).....throught house- mst bed switches, smoke detector in upstairs bedroom, and various other locations
|
Issue PAID IN FULL permit | | | 1/17/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/17/2017 | | DONE |
|
|
|
This permit was created on the web by steve cooper
|