Final | 3/21/2017 | 3/21/2017 | 3/21/2017 | P | PASS |
Eric Story
|
|
|
Reinspect Phone #: ###-#### Inspection requested via web by Greg Idsinga Corrections fixed final ok
|
Final | 3/20/2017 | 3/20/2017 | 3/20/2017 | P | FAIL |
Eric Story
|
|
|
House in back of main home. Phone #: ###-#### Inspection requested via web by Greg Idsinga 210.8 Receptalces located within 6' of a sink shall have GFCI protection 110.25 lockout needed fro water heater or disc 344.30 RMC shall have support within 3' of panel 110.30 fix both w/p's
|
Permanent Service | 2/1/2017 | 2/1/2017 | 2/1/2017 | A | PASS |
Eric Story
|
|
|
corrections Phone #: ###-#### Inspection requested via web by Greg Idsinga p/s o/h n ok
|
Rough-In Permanent Service | 1/20/2017 | 1/20/2017 | 1/20/2017 | P | CANC |
Eric Story
|
|
|
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga Just rough-in at this time
|
Electrical Rough-In | 1/20/2017 | 1/20/2017 | 1/20/2017 | P | PASS |
Eric Story
|
|
|
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga Mother in law quarters ok cover
|
Permanent Service | 1/20/2017 | 1/20/2017 | 1/20/2017 | P | FAIL |
Eric Story
|
|
|
Mother in law quarters in the back Phone #: ###-#### Inspection requested via web by Greg Idsinga 408.36(d) Back fed devices shall be fastened in place(screw missing in main) 230.24 Shall maintain 18' from service drip loop to roof line
|
Issue PAID IN FULL permit | | | 1/18/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/18/2017 | | DONE |
|
|
|
This permit was created on the web by Greg Idsinga
|