Final | 2/22/2017 | 2/23/2017 | 2/23/2017 | A | PASS |
Tom Saunders
|
|
|
Todd Sellman is contact at ###-####. If he cannot be reached, call Mike Rossknecht at ###-#### Phone #: ###-#### Inspection requested via web by Todd Sellman...
clearances obtained...no corrections needed...ok to final
|
Rough-In Permanent Service | 1/24/2017 | 1/24/2017 | 1/24/2017 | P | NR |
Tom Saunders
|
|
|
Contact on site is Mike. This is just for the outside portion including the underground. Phone #: ###-#### Inspection requested via web by Todd Sellman...
disconnect mounted ok...no transformer set yet
|
Electrical Rough-In | 1/24/2017 | 1/24/2017 | 1/24/2017 | P | PASS |
Tom Saunders
|
|
|
Mike Phone #: ###-####....
ok to cover pipes to transformer
|
Conference | 1/23/2017 | 1/23/2017 | 1/23/2017 | P | DONE |
Rock A. Hudson
|
|
|
Please contact Todd Sellman to meet onsite for conference. ###-####. Phone #: ###-#### Inspection requested via web by Todd Sellman Contactor to add new 480 volt service to building. CT meter at outdoor transformer. Main disconnecting means outside on south side. Once on inside plans are to install a gutter to tap off and refeed existing disconnects. Issues BCC 4-05-32- Code violations not to be retained. 110.26(A)- Minimum work space shall be provided for all disconnecting means. 36" deep and 30" wide. 110.26(B)- Work space shall be clear of foriegn equipment, compressor encroaches on space. 404.8(A)- Max height of disconnecting means shall not exceed 6'7".
|
Issue PAID IN FULL permit | | | 1/23/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 1/23/2017 | | DONE |
|
|
|
This permit was created on the web by Todd Sellman
|