Final | 8/18/2017 | 8/21/2017 | 8/21/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake corrections made final ok
|
Final | 8/17/2017 | 8/18/2017 | 8/18/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake 210.52 A 2 (1) Fixed panels shall count as wall space. ( need recep right side of back slider fixed panel and right side of Front room fixed panel. 410.16. Recessed lighting in cloths closet shall have enclosed lamp.(laundry room closet. 210.70 A 3. Equipment rooms shall have lighting outlet.(Garage furnace room) 406.6 Receps and switches shall have cover plates installed. 110.3 B Listed equipment shall be installed per manufacturers specs.( Garage 3way locked out)
|
Rough-In Permanent Service | 3/6/2017 | 3/6/2017 | 3/6/2017 | P | PASS |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Ryan Wake Rough-in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 3/2/2017 | 3/3/2017 | 3/3/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Everything is complete except the patios not completed. Customer would like service and interior cover. Phone #: ###-#### Inspection requested via web by Ryan Wake WUI zone A. 210.52- Fixed panel of slider in family room counts as wall space and shall have a receptacle outlet installed within 6' of door. 300.4- All wiring run thru bored holes that do not maintain 1 1/4" of framing surface shall be protected from physical damage. Garage sensor wiring. Master stool fan shall have abrasion protection for NM cable. Remote hood shall have abrasion protection for cable. 300.15- Splices for temp hook up for furnaces shall be contained in a box. 400.8- Remote hood has flexible cord. Flexible cords shall not be installed in a attic space.
|
Issue PAID IN FULL permit | | | 2/12/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 2/12/2017 | | DONE |
|
|
|
This permit was created on the web by Ryan Wake
|