Permit Information
Permit NumberELE17-00416
StatusFinaled
Name A M E ELECTRIC
Site Address 1747 N FAIRMEADOW DR
Project Name 
Customer Number17014
ePlanReviewNo
Description
New: PROVIDE ELECTRICAL FOR VILLAGE CHARTER SCHOOL BLDG #1
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/9/20178/9/20178/9/2017PPASS
DetailsTom Saunders
CONTACT IS JOHN Phone #: ###-#### Inspection requested via web by Lori Stout...

job complete...ok to final
Final7/18/20177/18/20177/18/2017PPART
DetailsTom Saunders
partial final building only, all but pole lights
contact is John Phone #: ###-#### Inspection requested via web by Lori Stout....

partial final to final off all classrooms so can have occupency in rooms....pole lights left on this permit to complete final...also need to check A/C disconnects all labelled and hall drinking fountain GFI is readily accessible
Electrical Rough-In6/27/20176/27/20176/27/2017PPASS
DetailsTom Saunders
underground
contact is John Phone #: ###-#### Inspection requested via web by Lori Stout...

underground for parking lot lights...ok to cover
Electrical Rough-In5/23/20175/24/20175/23/2017ACANC
DetailsTom Saunders
CALL JOHN Phone #: ###-#### >> Inspection requested via web by Lori Stout Inspection cancelled from web by: Lori Stout
Electrical Rough-In5/19/20175/19/20175/19/2017PPASS
DetailsDaryl DeGrange
underground Phone #: ###-#### Inspection requested via web by Lori Stout Rough-in ok trench, That portion of trench parallel with Fairmeadow, from alley way, north to pull box west to first parking lot fixture
Rough-In Permanent Service5/12/20175/12/20175/12/2017PPASS
DetailsRock A. Hudson
In building 1 if you call John he we meet you in the back. Phone #: ###-#### Inspection requested via web by Sue Minick 200k rated fuses, no available fault current calculated yet but with fuses rated this high ok. p/s o/h n ok
Conference4/17/20174/17/20174/17/2017PPASS
DetailsTom Saunders
Height of Service Riser Phone #: ###-#### Inspection requested via web by Lori Stout...

discussed clearance of new service feeders..18' above back alley and parking area
Electrical Rough-In4/11/20174/11/20174/11/2017PPASS
DetailsTom Saunders
KINDERGARTEN CEILING FOR COVER CONTACT ON SITE IS JOHN Phone #: ###-#### Inspection requested via web by Lori Stout..

celing ok to cover
Electrical Rough-In3/30/20173/30/20173/30/2017PPASS
DetailsJames Ady
John Busnardo is the electrician working on site. Phone #: ###-#### Inspection requested via web by Sue Minick All building 1 minus kindergarden ceiling ok to cover
Issue PAID IN FULL permit  2/20/2017 DONE
Payment received via Govolutions
Application received  2/20/2017 DONE
This permit was created on the web by Lori Stout
First Notice8/9/20178/9/2017   
DetailsTom Saunders