Final | 5/3/2017 | 5/4/2017 | 5/4/2017 | A | PASS |
James Ady
|
|
|
I will contact you in the morning and schedule a time to meet you onsite Phone #: ###-#### Inspection requested via web by Matthew Dunay Corrections made Final ok
|
Final | 5/2/2017 | 5/2/2017 | 5/2/2017 | P | FAIL |
James Ady
|
|
|
We will call at noon to schedule a time to meet you onsite. Phone #: ###-#### Inspection requested via web by Matthew Dunay 352.30 APVC conduit shall be supported within 3ft of each junction box. 352.10 F PVC above ground and exposed to physical damage shall be sch80. 250.64 C. Grounding electrode conductor shall be continuous. (Array Grounding) 690.32G3(1)(2)&(3) Marking and labeling required.
|
Issue PAID IN FULL permit | | | 3/13/2017 | | DONE |
|
|
|
|
Application received | | | 3/10/2017 | | |
|
|
|
|