Final | 5/19/2017 | 5/19/2017 | 5/19/2017 | P | PASS |
James Ady
|
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk corrections made final ok
|
Final | 5/18/2017 | 5/19/2017 | 5/19/2017 | A | FAIL |
James Ady
|
|
|
Garage code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk 314.20 Boxes set back more than 1/4in shall have extension ring. (Up bath 2 gang) 210.8 GFCI shall be readily accessible. (Garage opener temp still installed)
|
Rough-In Permanent Service | 3/17/2017 | 3/20/2017 | 3/20/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk rough in ok p/s u/g n ok
|
Issue PAID IN FULL permit | | | 3/17/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/17/2017 | | DONE |
|
|
|
This permit was created on the web by Alan Lusk
|