Final | 1/25/2019 | 1/25/2019 | 1/25/2019 | A | PASS |
James Ady
|
|
|
Please call 30 minutes in advance to ensure access to the property. Thank you Phone #: ###-#### Inspection requested via web by Casey Fouts Final ok
|
Rough-In Permanent Service | 4/24/2017 | 4/25/2017 | 4/25/2017 | P | PASS |
James Ady
|
|
|
Please call 30 min in advance so I can meet the inspector. Phone #: ###-#### Inspection requested via web by Casey Fouts Corrections on service made Rough in ok p/s o/h n ok
|
Permanent Service | 3/29/2017 | 3/29/2017 | 3/29/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Do not final out permit // Casey Phone #: ###-#### BCC 4-05-31(C)- Unfused conductors shall not run inside a structure unless for underground service entrance conductors for a recessed meter with 4 1/2' max length. 230.70- service disconnecting means shall be on outside or immediately on interior of structure. 230.28- Overhead service entrance conductors shall not attach to mast between weather head and a coupling.
|
Issue PAID IN FULL permit | | | 3/28/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 3/28/2017 | | DONE |
|
|
|
This permit was created on the web by Casey Fouts
|