Final | 7/26/2017 | 7/27/2017 | 7/27/2017 | A | PASS |
James Ady
|
|
|
garage code 0824 Phone #: ###-#### Inspection requested via web by Darryn Coburn Corrections made final ok
|
Final | 7/5/2017 | 7/6/2017 | 7/6/2017 | A | FAIL |
Rock A. Hudson
|
|
|
garage code 824 Phone #: ###-#### Inspection requested via web by Darryn Coburn 210.8- Washer receptacle with in 6' of a sink shall have GFCI protection. Butlers pantry GFI shall be readily accessible. 210.52(B)- No point along kitchen counter top shall be more than 24" from a receptacle outlet.
|
Rough-In Permanent Service | 4/11/2017 | 4/12/2017 | 4/13/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn rough in ok pending satisfaction of WUI zone A requirments by Building inspector. p/s u/g n ok
|
Issue PAID IN FULL permit | | | 4/7/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/7/2017 | | DONE |
|
|
|
This permit was created on the web by Darryn Coburn
|