Final | 7/6/2017 | 7/7/2017 | 7/7/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson...
ok to final
|
Rough-In Permanent Service | 5/1/2017 | 5/2/2017 | 5/2/2017 | A | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 4/30/2017 | 5/1/2017 | 5/1/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Therrin Robertson 210.52(A)- Arbor room enclosed need general layout for habitable room. Discussed at meeting with other inspectors and ruled if only used for green house purposes general receptacles not required however if finished sunroom type room 210.52(A) will be enforced. 300.4- NM cable shall be protected from damage where run thru bored holes that do not maintain 1 1/4" from framing surface. 352.6- All PVC pipe and fittings shall be listed. 2" expansion joint (Cantex 1 piece) not listed
|
Issue PAID IN FULL permit | | | 4/30/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 4/30/2017 | | DONE |
|
|
|
This permit was created on the web by Therrin Robertson
|