Permit Information
Permit NumberELE17-01279
StatusFinaled
Name GLENN ELECTRIC
Site Address 5779 E HOOTOWL DR
Project Name 
Customer Number 
ePlanReviewNo
Description
Complete Installation (includes room count and per: ROUGH AND PERM. SERVICE
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final8/15/20178/15/20178/15/2017PPASS
DetailsJames Ady
code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
Rough-In Permanent Service6/9/20176/9/20176/9/2017PPASS
DetailsMark Moncarr
Phone #: ###-#### Inspection requested via web by Bob Glenn p/s u/g n ok. All corrections made.
Rough-In Permanent Service6/8/20176/9/20176/9/2017AFAIL
DetailsRock A. Hudson
ready now. thanks Phone #: ###-#### Inspection requested via web by Bob Glenn
300.4- Where NM cable is run thru bored holes that do not maintain 1 1/4" from framing surface they shall be protected from physical damage. Nail plated needed.
Pantry notched stud, Master bed upper plate between windows, spare bed inside closet.
422.11- Furnace branch circuit shall be 20 amp as per manufacturers instructions.
Issue PAID IN FULL permit  5/2/2017 DONE
Payment received via Govolutions
Application received  5/2/2017 DONE
This permit was created on the web by Bob Glenn