First Notice | 6/23/2017 | 6/23/2017 | 7/22/2020 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Deb Gooden
|
Final | 6/23/2017 | 6/23/2017 | 6/23/2017 | P | PASS |
Rock A. Hudson
|
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Contractor seperated grounded and grounding at permenant service connection. Final ok
|
Permanent Service | 5/25/2017 | 5/25/2017 | 5/25/2017 | P | PASS |
James Ady
|
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden Corrections made p/s u/g n ok
|
Permanent Service | 5/12/2017 | 5/15/2017 | 5/15/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.9- Equipment shall be rated for fault current available at line terminals. 110.22- Disconnecting means shall be accurately labeled.
|
Permanent Service | 5/3/2017 | 5/3/2017 | 5/3/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Contact: Paul Wheeler Phone #: ###-#### Inspection requested via web by Deb Gooden 110.22- Disconnecting means shall be identifired as to its purpose. Address and or unit suppied. 110.24- Available fault current shall be posted prior to permenant service inspection. 250.24(A)(5)- A grounded conductor shall not be connected to normally non-current carrying metal parts of equipment. Seperation of grounds and neutrals in old panels which will be sub fed. 250.28- Grounding electrode conductors shall terminate with grounded conductors with main bonding jumper installed. 250.50- All available grounding electrodes described in 250.52 shall be used for grounding electode system. Wireman had not been on interior to confirm metal underground water pipe system. 250.92- Standard lock nuts shall not be only means of bonding metal raceways containing service entrance conductors. Bonding bushings required.
|
Issue PAID IN FULL permit | | | 5/2/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/2/2017 | | DONE |
|
|
|
This permit was created on the web by Deb Gooden
|