Final | 9/6/2017 | 9/6/2017 | 9/6/2017 | P | PASS |
Mark Moncarr
|
|
|
Code 2010 Phone #: ###-#### Inspection requested via web by Jason Wicks Ok final. Talked to contractor about brkr lockout on DW, and another strap on A/C whip. He will be working a job on this street tomorrow. Said he wold get it done.
|
Rough-In Permanent Service | 6/14/2017 | 6/14/2017 | 6/14/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks Corrections made rough in ok p/s u/g n ok
|
Electrical Rough-In | 6/13/2017 | 6/13/2017 | 6/13/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Shall pull seperate permit for temp pole. 210.52- Receptacle outlet needed with 6' of refer, outlet needed 2' wall by back door, outlet needed next to slider for 2 fixed panels. 300.4 nail plate up high by back door and windows. 310.15(B)(3)- Too many current carrying (10) conductors 1/2 wall by stairs. (9) max. 334.30- Powder bath outlet NM shall secure with in 12" of box. 334.12- NM shall not be installed where subject to physical damage. stair above runner. Homeruns run thru truss in garage ceiling. Truss company will issue how to proceed. Insulators started to insulate entry way, when asked to stop became difficult. Had conversation with general contractor told job is not approved for cover and shall not cover.
|
Change Status to I | | | 6/13/2017 | | DONE |
Christina Prado
|
|
|
Bar XL will pull seperate permit for temp power only. Will keep this open for full project
|
Temporary Service | 5/3/2017 | 5/3/2017 | 5/3/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks t/s u/g n ok
|
Issue PAID IN FULL permit | | | 5/3/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/3/2017 | | DONE |
|
|
|
This permit was created on the web by Jason Wicks
|