Permit Information
Permit NumberELE17-01320
StatusFinaled
Name UNITED ELECTRIC CONTRACTING
Site Address 515 W IDAHO ST
Project Name 
Customer NumberOCHOS
ePlanReviewNo
Description
Alteration: New Panel K, New Circuits in Kitchen & Bar Areas, Wiring to Evaporator for Walk-In Cooler, Wiring and Installation of Lights, New Dimmers, OC Sensors, Demo, Misc Receps & Power, Relocate Existing Meter Center to West Exterior Wall
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
First Notice6/7/20186/7/201812/19/2019 DONE
DetailsRock A. Hudson
Print Statement  12/19/2019 DONE
mailed
Final6/5/20186/7/20186/7/2018APASS
DetailsRock A. Hudson
Contact Tate Borstelman with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
Electrical Rough-In10/16/201710/17/201710/17/2017APASS
DetailsRock A. Hudson
Requesting inspection for cover in the bar only

Contact Tate Borstelman with any questions or comments - he will be on site

Thank you and have a nice day!
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Area noted bar wall rough in ok cover
Electrical Rough-In6/7/20176/7/20176/7/2017PPASS
DetailsRock A. Hudson
CONTACT TATE BORSTELMAN WITH ANY QUESTONS OR CONCERNS -

INSPECTION IS FOR KITCHEN ONLY - READY TO COVER Phone #: ###-#### Inspection requested via web by JENNY EMEL
kitchen/ prep area only walls and hardlid rough in ok cover.
Electrical Rough-In5/23/20175/24/20175/24/2017APASS
DetailsEric Story
Requested Inspection is for Cover for Walk In Cooler

Contact is Tate Borstelman ###-####
Phone #: ###-#### Inspection requested via web by JENNY EMEL
Walk in cooler in basement walls and ceiling only
ok cover
Permanent Service5/11/20175/11/20175/11/2017PPASS
DetailsRock A. Hudson
Re-Inspection of service panel moved from one location to another Phone #: ###-#### Inspection requested via web by JENNY EMEL
Main breaker B changed to 22k rating others to be changed Monday the15th as they are on order.
p/s u/g n ok
Permanent Service5/9/20175/10/20175/10/2017PFAIL
DetailsRock A. Hudson
Phone #: ###-#### Inspection requested via web by JENNY EMEL
110.24- Available fault current shall be posted prior to permenant service inspection to verify main disconnect rated for current available at line terminals as per 110.9. 10k rated main breakers.
10,959 L-L...8,217 L-N. Next size shall be installed.
Electrical Rough-In5/3/20175/3/20175/3/2017PPASS
DetailsRock A. Hudson
THIS REQUEST IS FOR UNDERGROUND READY TO COVER

Please contact Tate with any questions or concerns @ ###-####

Thank you and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL
Back area to be covered by an elevated deck creating 3' to 5' depth on underground. Rough in ok cover
Issue PAID IN FULL permit  5/3/2017 DONE
Payment received via Govolutions
Application received  5/3/2017 DONE
This permit was created on the web by JENNY EMEL