First Notice | 6/7/2018 | 6/7/2018 | 12/19/2019 | | DONE |
Rock A. Hudson
|
|
|
|
Print Statement | | | 12/19/2019 | | DONE |
|
|
|
mailed
|
Final | 6/5/2018 | 6/7/2018 | 6/7/2018 | A | PASS |
Rock A. Hudson
|
|
|
Contact Tate Borstelman with any questions Phone #: ###-#### Inspection requested via web by JENNY EMEL Final ok
|
Electrical Rough-In | 10/16/2017 | 10/17/2017 | 10/17/2017 | A | PASS |
Rock A. Hudson
|
|
|
Requesting inspection for cover in the bar only
Contact Tate Borstelman with any questions or comments - he will be on site
Thank you and have a nice day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Area noted bar wall rough in ok cover
|
Electrical Rough-In | 6/7/2017 | 6/7/2017 | 6/7/2017 | P | PASS |
Rock A. Hudson
|
|
|
CONTACT TATE BORSTELMAN WITH ANY QUESTONS OR CONCERNS -
INSPECTION IS FOR KITCHEN ONLY - READY TO COVER Phone #: ###-#### Inspection requested via web by JENNY EMEL kitchen/ prep area only walls and hardlid rough in ok cover.
|
Electrical Rough-In | 5/23/2017 | 5/24/2017 | 5/24/2017 | A | PASS |
Eric Story
|
|
|
Requested Inspection is for Cover for Walk In Cooler
Contact is Tate Borstelman ###-#### Phone #: ###-#### Inspection requested via web by JENNY EMEL Walk in cooler in basement walls and ceiling only ok cover
|
Permanent Service | 5/11/2017 | 5/11/2017 | 5/11/2017 | P | PASS |
Rock A. Hudson
|
|
|
Re-Inspection of service panel moved from one location to another Phone #: ###-#### Inspection requested via web by JENNY EMEL Main breaker B changed to 22k rating others to be changed Monday the15th as they are on order. p/s u/g n ok
|
Permanent Service | 5/9/2017 | 5/10/2017 | 5/10/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by JENNY EMEL 110.24- Available fault current shall be posted prior to permenant service inspection to verify main disconnect rated for current available at line terminals as per 110.9. 10k rated main breakers. 10,959 L-L...8,217 L-N. Next size shall be installed.
|
Electrical Rough-In | 5/3/2017 | 5/3/2017 | 5/3/2017 | P | PASS |
Rock A. Hudson
|
|
|
THIS REQUEST IS FOR UNDERGROUND READY TO COVER
Please contact Tate with any questions or concerns @ ###-####
Thank you and have a great day! Phone #: ###-#### Inspection requested via web by JENNY EMEL Back area to be covered by an elevated deck creating 3' to 5' depth on underground. Rough in ok cover
|
Issue PAID IN FULL permit | | | 5/3/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/3/2017 | | DONE |
|
|
|
This permit was created on the web by JENNY EMEL
|