Final | 12/6/2017 | 12/7/2017 | 12/7/2017 | A | PASS |
James Ady
|
|
|
Please call 30 min before arrival. Phone #: ###-#### Inspection requested via web by Jason Wicks final ok
|
Final | 12/5/2017 | 12/12/2017 | 12/5/2017 | P | CANC |
James Ady
|
|
|
Phone #: ###-#### >> Inspection requested via web by Jason Wicks Inspection cancelled from web by: Jason Wicks
|
Electrical Rough-In | 6/14/2017 | 6/14/2017 | 6/14/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks Corrections made rough in ok
|
Electrical Rough-In | 6/5/2017 | 6/5/2017 | 6/5/2017 | P | FAIL |
James Ady
|
|
|
Call Jason at ###-#### when you get there. Phone #: ###-#### Inspection requested via web by Jason Wicks 250.148 All grounding cond in box shall be tied together 404.9 b all switches shall be connected to egc 334.80 NM cables through bored holes shall be derated as per table 310.15 b. 334.30 Flat NM cable shall not be secured on edge and shall be supported every 4.5ft
|
Permanent Service | 5/12/2017 | 5/12/2017 | 5/12/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks p/s rec u/g n ok
|
Issue PAID IN FULL permit | | | 5/12/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/12/2017 | | DONE |
|
|
|
This permit was created on the web by Jason Wicks
|