Print Statement | | | 3/16/2018 | | DONE |
|
|
|
sent 2nd late notice 3-19-18
|
First Notice | 6/28/2017 | 6/28/2017 | 2/19/2018 | | DONE |
James Ady
|
|
|
This permit finaled on the web by Jason Wicks
|
Print Statement | | | 11/14/2017 | | DONE |
|
|
|
sent 1st late notice
|
Print Statement | | | 8/4/2017 | | DONE |
|
|
|
|
Final | 6/28/2017 | 6/28/2017 | 6/28/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks COrrections made final ok
|
Electrical Rough-In | 6/28/2017 | 6/28/2017 | 6/28/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks Ceiling only ok to cover
|
Final | 6/28/2017 | 6/28/2017 | 6/28/2017 | A | FAIL |
Eric Story
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks GFCI protection for drinking fountain&shall be readily accessible Face plates required Feild identification needed in panelboard
|
Electrical Rough-In | 5/16/2017 | 5/16/2017 | 5/16/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Jason Wicks corrections made Walls only ok to cover
|
Electrical Rough-In | 5/15/2017 | 5/15/2017 | 5/15/2017 | P | FAIL |
James Ady
|
|
|
This is the T-Mobile space, #8075. Phone #: ###-#### Inspection requested via web by Jason Wicks Cables shall be supported 1 1/4in away from face of stud. Several MC suppoted on edge of stud
|
Issue PAID IN FULL permit | | | 5/15/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 5/15/2017 | | |
|
|
|
|
Application received | | | 5/15/2017 | | DONE |
|
|
|
This permit was created on the web by Jason Wicks
|