Final | 7/17/2017 | 7/18/2017 | 7/18/2017 | A | PASS |
Rock A. Hudson
|
|
|
Garage Code 5233 or 5288 Phone #: ###-#### Inspection requested via web by Ben Grundhauser Final ok
|
Rough-In Permanent Service | 5/22/2017 | 5/23/2017 | 5/23/2017 | A | PASS |
James Ady
|
|
|
Questions ask for Ben Phone #: ###-#### Inspection requested via web by Ben Grundhauser Corrections made Rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 5/18/2017 | 5/19/2017 | 5/19/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Questions ask for Ben Phone #: ###-#### Inspection requested via web by Ben Grundhauser 300.4- NM and other cables shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface. Above panels in garage. to front recept. out entry. 334.30- Flat cables shall not be stapled on edge. 210.52(B)- If counter space is present at time of final receptacle spacing for kitchen ounter top areas required. * WUI zone A construction for cans in outer soffits.
|