Final | 7/12/2017 | 7/12/2017 | 7/12/2017 | A | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn...
ok to final
|
Rough-In Permanent Service | 5/23/2017 | 5/23/2017 | 5/23/2017 | P | PASS |
Tom Saunders
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn...
rough ok to cover p/s u/g n ok
|
Rough-In Permanent Service | 5/22/2017 | 5/23/2017 | 5/23/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 300.4- Where MN cable is run thru bored holes that do not maintain 1 1/4" from framing surface shall be protected from physical damage by nail plates. 45 degree corners. 300.15- Splice point to concrete encased electrode shall be accessible. Provide mudring. 725.136- Class 2 wiring shall not occupy same box unless seperated by a barrier. Kitchen 4 gang.
|
Issue PAID IN FULL permit | | | 5/19/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/19/2017 | | DONE |
|
|
|
This permit was created on the web by Bob Glenn
|