Print Statement | | | 11/30/2017 | | DONE |
|
|
|
|
First Notice | 6/27/2017 | 6/27/2017 | 8/10/2017 | | DONE |
Rock A. Hudson
|
|
|
This permit finaled on the web by Brad Baker
|
Final | 6/26/2017 | 6/27/2017 | 6/27/2017 | A | PASS |
Rock A. Hudson
|
|
|
everything should be good to go Phone #: ###-#### Inspection requested via web by Brad Baker Final ok
|
Final | 6/25/2017 | 6/26/2017 | 6/26/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Sorry had to cancel the AM request and move it to PM we didn''t quite get done Friday, should be ready by after noon thanks Brad Phone #: ###-#### Inspection requested via web by Brad Baker 210.8- All 120 volt 15 or 20 amp receptacle outlets located with in 6' of a sink shall have GFCI protection. 314.30- All boxes shall be secured in place. 330.30 MC shall be secured with in 12" of a box,
|
Final | 6/22/2017 | 6/26/2017 | 6/25/2017 | A | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### >> Inspection requested via web by Brad Baker Inspection cancelled from web by: Brad Baker
|
Electrical Rough-In | 5/25/2017 | 5/25/2017 | 5/25/2017 | P | PASS |
Eric Story
|
|
|
We would like a rough in for cover on the ceilings that are going to be drywalled thank you Phone #: ###-#### Inspection requested via web by Brad Baker Hard lid ceilings throughout ok cover
|
Electrical Rough-In | 5/23/2017 | 5/24/2017 | 5/24/2017 | A | PASS |
Mark Moncarr
|
|
|
Rough in for wall cover is ready the ceiling will be open and some grid thanks Brad Please call with any questions Phone #: ###-#### Inspection requested via web by Brad Baker Ok cover walls, bath lid and small soffit on E wall
|
Issue PAID IN FULL permit | | | 5/23/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Owner Supplied Equipment | | | 5/23/2017 | | |
|
|
|
|
Application received | | | 5/23/2017 | | DONE |
|
|
|
This permit was created on the web by Brad Baker
|