Final | 7/20/2017 | 7/20/2017 | 7/20/2017 | P | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Kevin Perez final ok
|
Permanent Service | 7/12/2017 | 7/13/2017 | 7/13/2017 | A | PASS |
James Ady
|
|
|
please call Rob if there are any issues in service. Phone #: ###-#### Inspection requested via web by Kevin Perez p/s u/g n ok
|
Final | 7/10/2017 | 7/10/2017 | 7/10/2017 | P | NR |
James Ady
|
|
|
Call Rob with any questions, at ###-#### Phone #: ###-#### Inspection requested via web by Kevin Perez Needed Perm serv. Cant final without service being energized.
|
Permanent Service | 7/10/2017 | 7/10/2017 | 7/10/2017 | P | FAIL |
James Ady
|
|
|
Call Rob with any questions, at ###-#### Phone #: ###-#### Inspection requested via web by Kevin Perez 110.24 Available Fault current shall be marked in the field. 110.9 Interrupting rating. Equipment intended to interrupt current at fault levels shall have a rating at least equal to available fault current.
|
Electrical Rough-In | 5/31/2017 | 5/31/2017 | 5/31/2017 | P | PASS |
Mark Moncarr
|
|
|
Please Call Rob P. Phone #: ###-#### Inspection requested via web by Kevin Perez Ok cover ground works E side of parking lot by dumpsters.
|
Issue PAID IN FULL permit | | | 5/30/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/30/2017 | | DONE |
|
|
|
This permit was created on the web by Kevin Perez
|
First Notice | 7/20/2017 | 7/20/2017 | | | |
James Ady
|
|
|
|