Final | 9/6/2017 | 9/7/2017 | 9/7/2017 | A | PASS |
Mark Moncarr
|
|
|
Code for garage-3255...key for house located on the 4x4 white trim on the right side of the door on side of home. Phone #: ###-#### Inspection requested via web by Greg Traudt Ok final
|
Rough-In Permanent Service | 6/4/2017 | 6/5/2017 | 6/5/2017 | P | PASS |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in ok cover p/s u/g n ok
|
Rough-In Permanent Service | 6/2/2017 | 6/2/2017 | 6/2/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 110.3- Furnace junction box cover removed. Reinstall box as provided by manufacture. 250.148- In boxes with more than 1 circuit all equipment grounding conductors shall be bonded together in that box. 300.4- NM cable shall be protected from physical damage where run thru bored holes that do not maintain 1 1/4" from framing surface. 314.25- Kitchen can has junction box cover not completely covering opening. 334.15- Wher NM cable is installed on stairway it is subject to damage when drywall is being installed. Relocate. 408.7- Unused breaker space in basement panel shall be sealed. Garage has only 2 circuits, if more than 2 grounding electode connection required.
|
Reinspection Fee (no hold) | 6/2/2017 | 6/2/2017 | 6/2/2017 | P | CANC |
Rock A. Hudson
|
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt Re-inspection fee assessed for incomplete floor in master bath and island cabinet incomplete. Cancel assessed to wrong address.
|
Issue PAID IN FULL permit | | | 5/31/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 5/31/2017 | | DONE |
|
|
|
This permit was created on the web by Greg Traudt
|