Final | 11/9/2017 | 11/9/2017 | 11/9/2017 | P | PASS |
Rock A. Hudson
|
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson Final ok
|
Final | 11/2/2017 | 11/2/2017 | 11/2/2017 | P | FAIL |
Rock A. Hudson
|
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson Corrections not complete. Master bath and powder bath receptacles not working and upstairs main bath shall have GFCI protection as per 210.8.
|
Final | 10/19/2017 | 10/20/2017 | 10/20/2017 | A | FAIL |
Rock A. Hudson
|
|
|
Garage code is JAYO enter Phone #: ###-#### Inspection requested via web by Zane Robertson 110.14- Dissimilar metals shall have an identified connector at splice. Aluminum/copper range wire in panel and receptacle. 210.8- washer receptacle located with in 6' of a sink shall have GFCI protection. Up bath receptacles shall have GFCI protection. Powder bath receptacle not working. 300.15- Box in garage shall be a cover. 404.9(A), 406.6- Switch and receptacle covers shall be in place at time of final.
|
Rough-In Permanent Service | 6/14/2017 | 6/15/2017 | 6/15/2017 | A | PASS |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson Corrections made rough in ok p/s u/g n ok
|
Rough-In Permanent Service | 6/13/2017 | 6/14/2017 | 6/14/2017 | A | FAIL |
James Ady
|
|
|
Phone #: ###-#### Inspection requested via web by Zane Robertson Remove Panel from warm wall
|
Issue PAID IN FULL permit | | | 6/13/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/13/2017 | | DONE |
|
|
|
This permit was created on the web by Zane Robertson
|