Final | 10/23/2017 | 10/23/2017 | 10/23/2017 | A | PASS |
Tom Saunders
|
|
|
Please call Von 1/2 prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen...core/shell ok to final
|
Final | 10/20/2017 | 10/20/2017 | 10/20/2017 | A | NR |
Tom Saunders
|
|
|
Please call Von 1/2 hour prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen...concrator has things to finish and safe off for core and shell final
|
Electrical Rough-In | 9/29/2017 | 9/29/2017 | 9/29/2017 | P | PASS |
Tom Saunders
|
|
|
Ceiling Cover. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen...
grid front entry, canopy, and one office ok to cover
|
Electrical Rough-In | 9/27/2017 | 9/27/2017 | 9/27/2017 | P | PASS |
Tom Saunders
|
|
|
UG to Sign.. Von is the onsite Contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...ok to cover
|
Permanent Service | 9/11/2017 | 9/12/2017 | 9/12/2017 | A | PASS |
Rock A. Hudson
|
|
|
Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen 15k max available, not posted but label being made. At time of final grade all disconnects will be below 6'7". 2 of the 2" conduits at bottom no glued in place, check next trip. p/s u/g n ok
|
Electrical Rough-In | 8/24/2017 | 8/24/2017 | 8/24/2017 | P | PASS |
Rock A. Hudson
|
|
|
Interior walls on south 1/2 are included in core and shell print. Interior wall rough in ok cover south 1/2
|
Electrical Rough-In | 8/23/2017 | 8/24/2017 | 8/24/2017 | A | PART |
Rock A. Hudson
|
|
|
Von. Wall Cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Asked for all walls possible, only BLD found is for core and shell only. Modifications are being done to core and shell. When modification review complete if chenges needed they shall be completed. Each TI requires seperate BLD and ELE permits. Exterior core and shell walls only rough in ok cover
|
Electrical Rough-In | 8/22/2017 | 8/23/2017 | 8/23/2017 | A | PASS |
Rock A. Hudson
|
|
|
Von. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy Discussed 300.4(E)- IMC minimum required where raceway is installed with in 1 1/2" of lowest part of roof deck. Also building steel shall be included as part of grounding electrode system. Bath walls and hardlids only rough in ok cover
|
Electrical Rough-In | 7/17/2017 | 7/17/2017 | 7/17/2017 | P | PASS |
Tom Saunders
|
|
|
UG cover. Please call Von 1/2 prior to arrival. Thanks Phone #: ###-#### Inspection requested via web by Buster Bowen...
slab UG ok to cover
|
Electrical Rough-In | 7/12/2017 | 7/12/2017 | 7/12/2017 | P | PASS |
Tom Saunders
|
|
|
Underground Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen....
perrimeter unground and service stubs....ok
|
Temporary Service | 6/30/2017 | 7/3/2017 | 7/3/2017 | A | CANC |
Eric Story
|
|
|
Temp construction power. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen Need t/s permit for this.
|
Electrical Rough-In | 6/26/2017 | 6/26/2017 | 6/26/2017 | P | PASS |
Tom Saunders
|
|
|
Von. Uffer ground inspection. Phone #: ###-#### Inspection requested via web by Sean DeLacy...
uffer ground...stranded copper...ok to cover
|
Issue PAID IN FULL permit | | | 6/20/2017 | | DONE |
|
|
|
Payment received via Govolutions
|
Application received | | | 6/20/2017 | | DONE |
|
|
|
This permit was created on the web by Buster Bowen
|
First Notice | 10/23/2017 | 10/23/2017 | | | |
Tom Saunders
|
|
|
|