Permit NumberELE17-01935
StatusFinaled
Name R M E INC
Site Address 8727 W ARDENE ST
Project Name 
Customer Number 
ePlanReviewNo
Description
New: Install power, lighting, and HVAC connections per drawings.
Contact Information
See Activities list for contact information
Show Inspection Activities Only
DescriptionReceivedRequestedCompletedAM/PMDispositionAssigned To 
Final10/23/201710/23/201710/23/2017APASS
DetailsTom Saunders
Please call Von 1/2 prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen...core/shell ok to final
Final10/20/201710/20/201710/20/2017ANR
DetailsTom Saunders
Please call Von 1/2 hour prior to arrival. Phone #: ###-#### Inspection requested via web by Buster Bowen...concrator has things to finish and safe off for core and shell final
Electrical Rough-In9/29/20179/29/20179/29/2017PPASS
DetailsTom Saunders
Ceiling Cover. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen...

grid front entry, canopy, and one office ok to cover
Electrical Rough-In9/27/20179/27/20179/27/2017PPASS
DetailsTom Saunders
UG to Sign.. Von is the onsite Contact. Phone #: ###-#### Inspection requested via web by Buster Bowen...ok to cover
Permanent Service9/11/20179/12/20179/12/2017APASS
DetailsRock A. Hudson
Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
15k max available, not posted but label being made. At time of final grade all disconnects will be below 6'7". 2 of the 2" conduits at bottom no glued in place, check next trip. p/s u/g n ok
Electrical Rough-In8/24/20178/24/20178/24/2017PPASS
DetailsRock A. Hudson
Interior walls on south 1/2 are included in core and shell print. Interior wall rough in ok cover south 1/2
Electrical Rough-In8/23/20178/24/20178/24/2017APART
DetailsRock A. Hudson
Von. Wall Cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Asked for all walls possible, only BLD found is for core and shell only. Modifications are being done to core and shell. When modification review complete if chenges needed they shall be completed. Each TI requires seperate BLD and ELE permits. Exterior core and shell walls only rough in ok cover
Electrical Rough-In8/22/20178/23/20178/23/2017APASS
DetailsRock A. Hudson
Von. Wall cover. Phone #: ###-#### Inspection requested via web by Sean DeLacy
Discussed 300.4(E)- IMC minimum required where raceway is installed with in 1 1/2" of lowest part of roof deck. Also building steel shall be included as part of grounding electrode system. Bath walls and hardlids only rough in ok cover
Electrical Rough-In7/17/20177/17/20177/17/2017PPASS
DetailsTom Saunders
UG cover. Please call Von 1/2 prior to arrival. Thanks Phone #: ###-#### Inspection requested via web by Buster Bowen...

slab UG ok to cover
Electrical Rough-In7/12/20177/12/20177/12/2017PPASS
DetailsTom Saunders
Underground Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen....

perrimeter unground and service stubs....ok
Temporary Service6/30/20177/3/20177/3/2017ACANC
DetailsEric Story
Temp construction power. Von is the onsite contact Phone #: ###-#### Inspection requested via web by Buster Bowen
Need t/s permit for this.
Electrical Rough-In6/26/20176/26/20176/26/2017PPASS
DetailsTom Saunders
Von. Uffer ground inspection. Phone #: ###-#### Inspection requested via web by Sean DeLacy...

uffer ground...stranded copper...ok to cover
Issue PAID IN FULL permit  6/20/2017 DONE
Payment received via Govolutions
Application received  6/20/2017 DONE
This permit was created on the web by Buster Bowen
First Notice10/23/201710/23/2017   
DetailsTom Saunders